Skip to content
Pneumatics & compressed air

Compressed air quality and ISO 8573-1: purity classes, pressure dew point and where to fix the water

ISO 8573-1 writes air quality as three numbers — particles, water, oil. What [2:4:2] or [7:4:3] actually means, which classes food, paint, tools and valves are commonly specified at, why hot, humid air drops so much water once it is compressed and cooled, and why drains, coalescing filters and dryers — not the FRL at the machine — are where water is removed.

Written by
Ayush Bhatia, Director
Published
Reading
14 min · 6 sections
Share
A clear-bowl filter on a compressed-air line draining condensate into a floor grate, an air dryer behind it
Water condenses out of compressed air as it cools; drains and dryers are where it should leave the system.

At a glance

Key takeaways

  1. ISO 8573-1:2010 grades compressed air with three class numbers, written [particles:water:oil]. Lower is cleaner; class 0 is a limit the user or supplier specifies, stricter than class 1.
  2. Water classes 1–6 are pressure dew points, from −70 °C (class 1) to +10 °C (class 6); classes 7–9 are liquid water content. Oil classes 1–4 run from 0.01 to 5 mg/m³ total oil.
  3. Air is compressed hot and then cooled, and cooled air cannot hold the water it carried in. The Compressed Air Challenge notes air leaving an aftercooler is normally saturated.
  4. Water is removed centrally — drains, a dryer to set the pressure dew point, and coalescing filters for oil. A point-of-use FRL catches what is left; it cannot dry a wet system.
  5. There is no single correct class for an application. Specify the class the equipment maker or your industry guideline asks for, and size the treatment to that.

Figures verified · Classes from ISO 8573-1:2010 as reproduced by MAC Valves, Atlas Copco and EXAIR; dew point and dryer figures from the Compressed Air Challenge and Sullair. Application classes are published examples, not requirements.

Specify “clean, dry air” and every supplier will agree to it. Specify ISO 8573-1:2010 [2:4:2] and you have said exactly how many particles, how dry and how much oil — something a dryer and filter train can be designed to, and a test can confirm. This guide explains how to read the classes, what typical uses ask for, and where in a system each contaminant should actually be removed.

/01How to read a purity class.

ISO 8573-1 is part 1 of the ISO 8573 series on compressed air: it defines the purity classes, and the other parts describe how each contaminant is measured. The current edition is 2010. It deals with three contaminants, and each gets its own class number:

  • Particles — solid particles, counted per cubic metre in three size bands (classes 1–5), or by mass concentration (classes 6–7).
  • Water — as a pressure dew point for classes 1–6, or as liquid water content for classes 7–9.
  • Oil — total oil: aerosol, liquid and vapour together, in mg/m³ (classes 1–4).

A specification is written as the standard plus the three numbers in that order: ISO 8573-1:2010 [A:B:C], where A is the particle class, B the water class and C the oil class. MAC Valves, for example, gives its minimum air quality recommendation for its valves as [7:4:3]: particle class 7, a pressure dew point of +3 °C (+37 °F), and no more than 1 mg/m³ of oil.

Lower numbers are cleaner. Class 0 does not mean zero contamination: it means a limit specified by the equipment user or supplier that is stricter than class 1. A class 0 claim is only meaningful with that agreed limit stated next to it.

ISO 8573-1:2010 purity classes (maximum values; as reproduced by MAC Valves and checked against Atlas Copco and EXAIR)
ClassParticles 0.1–0.5 µm per m³Particles 0.5–1 µm per m³Particles 1–5 µm per m³WaterTotal oil
0As specified by the user or supplier, stricter than class 1——As specified, stricter than class 1As specified, stricter than class 1
1Highlighted≤ 20,000≤ 400≤ 10Pressure dew point ≤ −70 °C (−94 °F)≤ 0.01 mg/m³
2≤ 400,000≤ 6,000≤ 100PDP ≤ −40 °C (−40 °F)≤ 0.1 mg/m³
3Not specified≤ 90,000≤ 1,000PDP ≤ −20 °C (−4 °F)≤ 1 mg/m³
4Not specifiedNot specified≤ 10,000PDP ≤ +3 °C (+37 °F)≤ 5 mg/m³
5Not specifiedNot specified≤ 100,000PDP ≤ +7 °C (+45 °F)—
6By mass: ≤ 5 mg/m³——PDP ≤ +10 °C (+50 °F)—
7By mass: 5–10 mg/m³——Liquid water ≤ 0.5 g/m³—
8———Liquid water 0.5–5 g/m³—
9———Liquid water 5–10 g/m³—

/02What typical uses ask for.

The standard sets the scale; it does not say which class an application needs. That comes from the equipment maker, an industry guideline, or your own process risk. Published examples give a sense of the range — but they are examples, and the sources do not always agree, so treat them as a starting point for a conversation rather than a specification.

Published examples of specified classes — check the current guideline or maker requirement for your case
UseClass [particles:water:oil]Source
Food and beverage, air in direct contact with productHighlighted[2:2:1]BCAS/BRC guideline BPG 102, as reported by Atlas Copco and EXAIR
Food and beverage, indirect contact (packaging, containers)[2:4:2]BPG 102, as reported by Atlas Copco and EXAIR; a 2006 report of the first edition gives [2:4:1]
Food and beverage; pharmaceuticals[1:2:1]Atlas Copco application examples
Clean-room assembly[1:1:1]EXAIR example
Textile machinery[4:4:3]Atlas Copco application examples
General pneumatic tools[3:4:4]Atlas Copco application examples
Pneumatic valves (minimum)[7:4:3]MAC Valves recommendation for its products

Two things stand out. First, the water class does most of the work: the difference between a factory air supply and a food-contact supply is mainly how dry it is and how little oil it carries. Second, these are classes at the point of use. A dryer outlet can meet a class that the air no longer meets after fifty metres of carbon-steel pipe, so the class is specified, and tested, where the air is used.

/03Pressure dew point, and why compressed air makes water.

All atmospheric air carries water vapour, and how much it can carry depends on two things: temperature and pressure.

  • Temperature. Warm air holds more water vapour than cool air. The Compressed Air Challenge gives the rule of thumb that the moisture content of saturated air roughly doubles for every 20 °F (about 11 °C) rise — saturated air at 100 °F holds almost twice the moisture of saturated air at 80 °F.
  • Pressure. Compressed air holds less vapour per unit volume. Sullair puts it this way: compressing air from atmospheric pressure to 100 psig raises the pressure nearly eightfold, so at the same temperature the compressed air can hold only about one-eighth of the moisture it held at ambient conditions.

Compression squeezes all the water the intake air carried into a fraction of its volume. It does not condense immediately, because compression also heats the air — Sullair notes discharge air is commonly 190 °F or more — and hot air holds more vapour. The Compressed Air Challenge describes what happens next: condensation generally does not occur inside the compression element, but begins as the air is cooled in the aftercooler, and the air leaving the aftercooler is normally 100% saturated at the aftercooler’s outlet temperature. As that saturated air cools further towards ambient in the receiver and pipes, more water drops out.

That is the meaning of pressure dew point (PDP): the temperature, at line pressure, to which the compressed air can be cooled before its water vapour starts to condense. It is the number that matters for compressed air. Atlas Copco points out that it is higher than the atmospheric dew point of the same air, because compression has concentrated the moisture — so a dew point quoted at atmospheric pressure cannot be compared with one quoted at line pressure. The rule for any system is simple: if any part of the pipework is colder than the air’s pressure dew point, water will condense there.

What this means on a hot, humid site

In the Gulf the intake air is often both hot and humid, and an air-cooled aftercooler can only cool the air to somewhere above the ambient temperature. The Compressed Air Challenge notes the air entering a dryer is usually close to the temperature at which it left the aftercooler. Hot, saturated air at the dryer inlet therefore carries far more water — by the doubling rule above — than the same compressor delivers on a cool day, and a dryer selected on standard inlet conditions can be overloaded. Air that leaves a hot compressor house and then runs through an air-conditioned building, or cools overnight, keeps dropping water in the pipework for the same reason.

/04Where to fix the water: drains, filters and dryers.

The cheapest place to remove water is where it first appears, in bulk, near the compressor. Treatment works from the compressor outwards:

  1. Separate and drain at the aftercooler and receiver. The Compressed Air Challenge stresses that condensed moisture must be removed by an efficient separator and trap. Receivers, separators and drip legs need drains that open reliably — timed electric or zero-loss level-sensing drains rather than a manual valve someone has to remember.
  2. Dry the air to the dew point you need. The dryer sets the water class. The Compressed Air Challenge gives typical dew points, at operating pressure and a saturated inlet of 100 °F: refrigerated dryers 35 °F or 50 °F (about +2 °C or +10 °C — water class 4 or 6), regenerative desiccant dryers −40 °F or lower (−40 °C, class 2), and deliquescent dryers 64 to 80 °F. It also advises drying air only to the level the plant equipment or ambient conditions require, and drying at the highest pressure the design allows, because saturated air at higher pressure holds less water per standard cubic foot.
  3. Filter for particles and oil. Main-line coalescing filters take out oil aerosols and fine particles and set the oil class; activated-carbon filters remove oil vapour. Filters ahead of a dryer protect it, and a filter after a desiccant dryer catches desiccant dust.
  4. Drain the low points. Take branch lines off the top of the header so that any water in the main runs past rather than down into the branch, and drain the low points.

The point-of-use FRL: the last line

The FRL at the machine is the final guard, not the treatment plant. Its filter catches the water that condensed in the pipe after the dryer, plus rust and scale from the pipe itself; a coalescing element at the machine gives the final oil class for a sensitive load. If the bowl at the machine is filling with water every shift, the cure is upstream — a dryer that is undersized, bypassed or failed, or a drain that is not draining. Our FRL guide covers point-of-use filters, drains and bowls in detail.

What each stage controls
StageControlsTypical locationWhat it cannot do
Separator and condensate drainBulk liquid waterAftercooler, receiver, drip legsRemove vapour; lower the dew point
Refrigerated dryerHighlightedWater class 4–6 (PDP about +2 to +10 °C)After the receiverReach a sub-zero dew point
Desiccant dryerWater class 2 or better (PDP −40 °C or lower)After the receiver, with filters either sideRemove oil vapour
Coalescing filterOil aerosol and fine particles (oil and particle class)Main line and point of useDry the air
Activated-carbon filterOil vapour and odourAfter a coalescing filterHandle liquid water or bulk oil
Point-of-use FRLResidual liquid water, pipe scale, pressureAt each machineFix a wet or oily supply

/05Writing the specification.

A good air-quality specification is short:

  • the standard and edition — ISO 8573-1:2010;
  • the class as three numbers, [particles:water:oil], taken from the equipment maker or the guideline that governs the process;
  • where the class applies — at the dryer outlet, in the header, or at the point of use;
  • for water, the line pressure at which the dew point is stated.

Then size each stage for the worst case it will see: the highest inlet temperature, the highest humidity and the peak flow, not the nameplate conditions.

Where is the water (or oil) coming from?

  1. IfWater in every FRL bowl across the plant?

    Supply problem. Check the dryer is running, not bypassed and sized for hot-season inlet temperature; check receiver and separator drains.

  2. IfWater only at machines far from the compressor or in cooler areas?

    The pipe is colder than the pressure dew point. Lower the dew point or drain the low points; branch off the top of the header.

  3. IfOil film or smell at the point of use?

    Main-line coalescing filter, then activated carbon for vapour; check elements are not saturated.

  4. IfFood, pharmaceutical or paint air?

    Specify the class from the governing guideline or maker; usually a desiccant or refrigerated dryer plus coalescing and carbon filtration, with point-of-use coalescing.

  5. IfGeneral automation valves and cylinders?

    Check the valve maker’s minimum — MAC asks for [7:4:3] — and a point-of-use 40 µm or 5 µm filter-regulator.

Common questions

What does ISO 8573-1 class 1.4.1 mean?
Particle class 1 (no more than 20,000, 400 and 10 particles per m³ in the 0.1–0.5, 0.5–1 and 1–5 µm bands), water class 4 (pressure dew point +3 °C or lower), and oil class 1 (no more than 0.01 mg/m³ total oil).
What is class 0 in ISO 8573-1?
A limit agreed by the equipment user or supplier that is stricter than class 1. It is not a fixed number and not “zero”, so a class 0 claim should always state the agreed limit.
What is the difference between pressure dew point and atmospheric dew point?
Pressure dew point is the temperature, at line pressure, at which water starts to condense from the compressed air. It is higher than the atmospheric dew point of the same air because compression concentrates the moisture. Always state the pressure with a dew point.
Why is there so much water in compressed air?
Compression packs the water vapour from a large volume of intake air into a small one. Hot air from the compressor holds it as vapour, but once the air is cooled in the aftercooler and pipes it cannot, and the excess condenses. Hot, humid intake air makes more of it.
What class of compressed air is required for food?
The BCAS/BRC food-grade guideline (BPG 102) is reported as specifying [2:2:1] for air in direct contact with food and [2:4:2] for indirect contact. Check the current edition and your own food-safety plan.
Will a coalescing filter remove water from compressed air?
It removes liquid water and water aerosol that are already in the air, but it does not lower the dew point. Vapour that passes through will condense further downstream if the line cools. Use a dryer to control water.
What dew point does a refrigerated dryer give?
The Compressed Air Challenge gives 35 °F or 50 °F (about +2 °C or +10 °C) at operating pressure with a saturated inlet at 100 °F — roughly water class 4 to 6. For a sub-zero dew point you need a desiccant dryer, typically −40 °F (−40 °C) or lower.

/06What we list.

Main-line and point-of-use filters, coalescing elements, condensate drains and filter-regulators from the makers on our air preparation shelf that build them — Parker, Wilkerson, Norgren, Hankison, Ingersoll Rand, Metal Work, Nitra, SMC, Texas Pneumatic Tools, Dynaquip and Conrader — each by maker part number:

Filters and drains

What next

  1. 01
  2. 02
  3. 03

    Where pneumatic parts like these go

    A pneumatic line stops for the smallest part — a valve coil, a cylinder seal kit, a regulator, a few metres of tube — and the machine builder is often half a world away. We quote by the maker part number on the nameplate or the bill of materials, match the voltage, port thread and tube size you run, and ship the whole list from Dubai as one consignment.

    Everything above ships from the same Dubai warehouse. If your destination is not listed, it is almost certainly still one we quote. See every export destination

Chasing water or oil in your air lines?

Tell us the flow, line pressure, the class you need at the point of use and what you are seeing in the bowls. We will quote main-line filters, elements, drains and point-of-use FRLs by maker part number.

Plant-down? Call +971 52 2477942 — 24/7

Keep reading

More on Pneumatics & compressed air

All articles in this topic
A vane air motor with planetary gearbox driving a mixer shaft over a stainless tank, fed through a regulator

Air motors: vane or piston, how the torque curve behaves, and how to size one at your pressure

12 min read

Nickel-plated brass push-in fittings with coloured release collars and blue tube, beside sintered bronze silencers

Push-to-connect fittings and exhaust silencers: how they grip, seal, release and slow a cylinder

12 min read

Back to Blog