Tank Emergency Vent, 16" to 24", API 2000

Emergency vents for storage tanks to API 2000: 16" to 24", weight-loaded (spring-loaded above 6.9 kPa), relieve the vapour from an external fire so the tank does not rupture.
Key features
- Valve type: Emergency vent, tank
- Construction: Weight- or spring-loaded cover
- Design standard: API 2000
- Size range: 16" to 24"
- Pressure class: Set 0.2 to 103.4 kPa; vacuum -0.2 to -1.7 kPa
- Body material: Carbon steel, stainless steel, carbon steel with PTFE
- End connections: Flanged
- Operation: Self-acting
- Valve type
- Emergency vent, tank
- Design standard
- API 2000
- Pressure class
- Set 0.2 to 103.4 kPa; vacuum -0.2 to -1.7 kPa
- End connections
- Flanged
- Operation
- Self-acting
Product description
A large hinged or lifting cover that relieves the vapour generated when a tank is exposed to fire, a flow far beyond what the breather valve can pass. Weight-loaded vents cover the usual low settings; above 6.9 kPa a spring-loaded design is used.
Storage tanks are built for only a few kilopascals of pressure or vacuum. As a tank fills, empties, heats or cools it breathes, and a breather valve lets it do so within those limits while keeping vapour losses and emissions down. Vents are sized to API 2000 for normal and emergency breathing.
Construction
- Weight-loaded cover; spring-loaded above 6.9 kPa
- Vacuum relief option to -1.7 kPa
- Large free area for fire-case relief
- Flanged to the tank manway or nozzle
Sizes and ratings
Published range: 16" to 24", Set 0.2 to 103.4 kPa; vacuum -0.2 to -1.7 kPa, in carbon steel, stainless steel, carbon steel with ptfe. End connections: Flanged. Operation: self-acting.
Each valve is sized to the relieving case; the data sheet and general arrangement drawing come with the quotation.
Testing and documents
Set-pressure and leakage tests to API 2000, with the material certificates and the pressure-test record supplied with the vent. Third-party inspection and extra tests are added when the order specifies them.
Supply
Emergency vents are supplied from Dubai to projects, plants and maintenance teams across the GCC, the wider Middle East and Africa. Most are built to the order specification, so delivery depends on size, class, material and operator; standard carbon-steel sizes move fastest. We review the data sheet before quoting and flag anything that needs clarifying, such as a missing pipe schedule or an operator torque that has not been sized.
Related valves
Other safety and relief valves in the range, for comparison when the duty is not settled yet: Nuclear Safety Valves: Pressurizer, Main Steam and Auxiliary System, Nuclear MSR Pilot-Operated Safety Valve and Vacuum Relief Valve, Conventional Safety Relief Valve, API 526, Orifice D to T, Balanced Bellows Safety Relief Valve, API 526.
Identification
| Parameter | Value |
|---|---|
| Valve type | Emergency vent, tank |
| Construction | Weight- or spring-loaded cover |
Standards
| Parameter | Value |
|---|---|
| Design standard | API 2000 |
| Pressure testing | Set-pressure and leakage tests to API 2000 |
Range
| Parameter | Value |
|---|---|
| Size range | 16" to 24" |
| Pressure class | Set 0.2 to 103.4 kPa; vacuum -0.2 to -1.7 kPa |
| Temperature range | -46 °C to 200 °C |
Materials
| Parameter | Value |
|---|---|
| Body material | Carbon steel, stainless steel, carbon steel with PTFE |
Construction
| Parameter | Value |
|---|---|
| End connections | Flanged |
| Operation | Self-acting |
Application
| Parameter | Value |
|---|---|
| Typical service | Fire-case emergency venting of storage tanks |
Supply
| Parameter | Value |
|---|---|
| Supply | Built to order and supplied from Dubai with material certificates and the test record |
Shipping & lead time
What is the Tank Emergency Vent, 16" to 24", API 2000 and what is it used for?▾
Does every tank need an emergency vent?▾
What sizes and pressure classes does the Tank Emergency Vent, 16" to 24", API 2000 cover?▾
Is the tank emergency vent re-closing?▾
What pressure and temperature range does the tank emergency vent work in?▾
What body materials does the tank emergency vent come in?▾
Which standards apply to the tank emergency vent, and how is it tested?▾
What end connections and operation does the tank emergency vent have?▾
How do I install and check a tank emergency vent?▾
How does the emergency vent differ from the tank pressure relief valve?▾
What documents come with the tank emergency vent, and can you supply against a project specification?▾
How is the tank emergency vent supplied, and how long does it take?▾
Shipped worldwide from our Dubai warehouse. Transit, routes and documentation for 136 destinations
From the blog