Low-Fin Copper-Alloy Tubes

Integral low-fin tubes in copper, admiralty brass and 90/10 and 70/30 copper-nickel to ASTM B359, with fin tips no larger than the plain end, for chillers, condensers and refrigerant evaporators. Made to ASTM B359/B359M, EN 12452. Supplied from Dubai with an Indus part number for each size and mill test certificates on request.
Key features
- Product type: Low-Fin Copper-Alloy Tubes
- Construction: Seamless drawn
- Standards: ASTM B359/B359M, EN 12452
- Base tube material: C12200; C70600; C71500; C44300
- Fin material: integral, rolled from the tube wall
- Outside diameter: 15.875–25.4 mm
- Wall thickness: 1.245–2.235 mm
- Product type
- Low-Fin Copper-Alloy Tubes
- Construction
- Seamless drawn
- Base tube material
- C12200; C70600; C71500; C44300
- Fin material
- integral, rolled from the tube wall
Product description
Integral low-fin tubes in copper, admiralty brass and 90/10 and 70/30 copper-nickel to ASTM B359, with fin tips no larger than the plain end, for chillers, condensers and refrigerant evaporators.
Specification
- Standard fin densities: 19 and 26 fpi standard; 11.5, 28, 30, 36, 43 fpi also catalogued
- Fin OD vs plain end: Fin tip diameter equals plain-end OD, so tubes fit tubesheets like plain tube
- 19 fpi fin height: 1.40 mm (0.055 in) avg, 1.27 mm (0.050 in) min; mean fin thickness 0.36 mm
- 26 fpi fin height: 1.245 mm (0.049 in)
- Low-fin materials incl. copper alloys: 90/10, 70/30, C44300 admiralty, copper
Standards
ASTM B359/B359M, EN 12452. Equivalent grades across ASTM, EN, DIN, JIS and GB/T standards are indicative; we check them against each tender.
Materials
- Tube: C12200; C70600; C71500; C44300
- Fins: integral, rolled from the tube wall
Testing and documents
- Tests to ASTM B359
- Mill test certificate to EN 10204 3.1 on request; third-party inspection can be arranged against your inspection and test plan
Where it is used
- Chillers
- Refrigerant (C3/propane) condensers in petrochemical and LNG plants
- Seawater-cooled boil-off condensers
Sizes
10 sizes, each under its own Indus part number in the size table. The table lists typical sizes for the range; other sizes are made on request.
Ordering
Quote the Indus part number from the size table, or send the standard and grade, the outside diameter and wall (BWG or millimetres, minimum or average wall), the length and the quantity. We quote with the mill certificates and the inspection you need.
Identification
| Parameter | Value |
|---|---|
| Product type | Low-Fin Copper-Alloy Tubes |
| Construction | Seamless drawn |
Compliance
| Parameter | Value |
|---|---|
| Standards | ASTM B359/B359M, EN 12452 |
Construction
| Parameter | Value |
|---|---|
| Base tube material | C12200; C70600; C71500; C44300 |
| Fin material | integral, rolled from the tube wall |
Dimensions
| Parameter | Value |
|---|---|
| Outside diameter | 15.875–25.4 mm |
| Wall thickness | 1.245–2.235 mm |
| Length | Random or fixed lengths; cut to length on request |
| Size table | Typical sizes — other sizes on request |
Quality
| Parameter | Value |
|---|---|
| Testing | Tests to ASTM B359 |
| Certification | Mill test certificate to EN 10204 3.1 on request; third-party inspection by arrangement |
Application
| Parameter | Value |
|---|---|
| Typical services | Chillers; Refrigerant (C3/propane) condensers in petrochemical and LNG plants; Seawater-cooled boil-off condensers |
Shipping & lead time
Sizes & part numbers
10 sizes- Indus part no.IH-TF-EC-LOF-0159-183-F159
- O.D. (mm)
- 15.875
- O.D. (in)
- 5/8
- Wall (mm)
- 1.829
- Fin O.D. (mm)
- 15.875
- Fin height (mm)
- 1.397
- Fins per inch
- 19
- Root dia. (mm)
- 13.081
- Wall under fin (mm)
- 1.245
- Outside area (m²/m)
- 0.126
- Indus part no.IH-TF-EC-LOF-0159-224-F159
- O.D. (mm)
- 15.875
- O.D. (in)
- 5/8
- Wall (mm)
- 2.235
- Fin O.D. (mm)
- 15.875
- Fin height (mm)
- 1.397
- Fins per inch
- 19
- Root dia. (mm)
- 13.081
- Wall under fin (mm)
- 1.651
- Outside area (m²/m)
- 0.126
- Indus part no.IH-TF-EC-LOF-0190-183-F190
- O.D. (mm)
- 19.050
- O.D. (in)
- 3/4
- Wall (mm)
- 1.829
- Fin O.D. (mm)
- 19.050
- Fin height (mm)
- 1.397
- Fins per inch
- 19
- Root dia. (mm)
- 16.256
- Wall under fin (mm)
- 1.245
- Outside area (m²/m)
- 0.153
- Indus part no.IH-TF-EC-LOF-0190-206-F190
- O.D. (mm)
- 19.050
- O.D. (in)
- 3/4
- Wall (mm)
- 2.057
- Fin O.D. (mm)
- 19.050
- Fin height (mm)
- 1.397
- Fins per inch
- 19
- Root dia. (mm)
- 16.256
- Wall under fin (mm)
- 1.473
- Outside area (m²/m)
- 0.153
- Indus part no.IH-TF-EC-LOF-0190-224-F190
- O.D. (mm)
- 19.050
- O.D. (in)
- 3/4
- Wall (mm)
- 2.235
- Fin O.D. (mm)
- 19.050
- Fin height (mm)
- 1.397
- Fins per inch
- 19
- Root dia. (mm)
- 16.256
- Wall under fin (mm)
- 1.651
- Outside area (m²/m)
- 0.153
- Indus part no.IH-TF-EC-LOF-0222-206-F222
- O.D. (mm)
- 22.225
- O.D. (in)
- 7/8
- Wall (mm)
- 2.057
- Fin O.D. (mm)
- 22.225
- Fin height (mm)
- 1.397
- Fins per inch
- 19
- Root dia. (mm)
- 19.431
- Wall under fin (mm)
- 1.473
- Outside area (m²/m)
- 0.181
- Indus part no.IH-TF-EC-LOF-0254-206-F254
- O.D. (mm)
- 25.400
- O.D. (in)
- 1
- Wall (mm)
- 2.057
- Fin O.D. (mm)
- 25.400
- Fin height (mm)
- 1.397
- Fins per inch
- 19
- Root dia. (mm)
- 22.606
- Wall under fin (mm)
- 1.473
- Outside area (m²/m)
- 0.209
- Indus part no.IH-TF-EC-LOF-0190-125-H012
- O.D. (mm)
- 19.050
- O.D. (in)
- 3/4
- Wall (mm)
- 1.245
- Fin O.D. (mm)
- —
- Fin height (mm)
- 1.245
- Fins per inch
- 26
- Root dia. (mm)
- 16.561
- Wall under fin (mm)
- 0.711
- Outside area (m²/m)
- 0.182
Show all 10 sizesShow fewer sizes
- Indus part no.IH-TF-EC-LOF-0190-147-H012
- O.D. (mm)
- 19.050
- O.D. (in)
- 3/4
- Wall (mm)
- 1.473
- Fin O.D. (mm)
- —
- Fin height (mm)
- 1.245
- Fins per inch
- 26
- Root dia. (mm)
- 16.561
- Wall under fin (mm)
- 0.889
- Outside area (m²/m)
- 0.182
- Indus part no.IH-TF-EC-LOF-0190-183-H012
- O.D. (mm)
- 19.050
- O.D. (in)
- 3/4
- Wall (mm)
- 1.829
- Fin O.D. (mm)
- —
- Fin height (mm)
- 1.245
- Fins per inch
- 26
- Root dia. (mm)
- 16.561
- Wall under fin (mm)
- 1.245
- Outside area (m²/m)
- 0.182
O.D. (mm) — Outside diameter of the tube or pipe in millimetres. O.D. (in) — The same outside diameter in inches, as the trade orders it. Wall (mm) — Wall thickness in millimetres: minimum or average wall per the governing standard and the order. Fin O.D. (mm) — Outside diameter over the fins in millimetres. Fin height (mm) — Height of the fin above the tube surface in millimetres. Fins per inch — Fin density in fins per inch; a band means any density in it can be made. Root dia. (mm) — Diameter at the root of the fins, in millimetres. Wall under fin (mm) — Average wall thickness under the fins, in millimetres. Outside area (m²/m) — Outside surface area per metre of finned length.
These are typical sizes for the range, not a full mill list. Other diameters, walls, fin geometries and lengths are made to order: tell us the standard and grade, the O.D. and wall, and the length you need. Mill test certificates to EN 10204 3.1 are available on request.
What are Low-Fin Copper-Alloy Tubes used for?▾
How do I read an Indus part number for Low-Fin Copper-Alloy Tubes, such as IH-TF-EC-LOF-0159-183-F159?▾
What sizes do Low-Fin Copper-Alloy Tubes come in?▾
What do I need to send to order Low-Fin Copper-Alloy Tubes to the right size and grade?▾
What tests and certificates come with Low-Fin Copper-Alloy Tubes?▾
Which materials and grades are Low-Fin Copper-Alloy Tubes available in?▾
Which standards apply to Low-Fin Copper-Alloy Tubes?▾
What do Low-Fin Copper-Alloy Tubes connect to or fit with?▾
How should Low-Fin Copper-Alloy Tubes be inspected on receipt and stored?▾
How do Low-Fin Copper-Alloy Tubes differ from Inner-Grooved Copper Tubes?▾
How are Low-Fin Copper-Alloy Tubes shipped, and can they be exported from Dubai?▾
Do you keep Low-Fin Copper-Alloy Tubes in stock in Dubai?▾
Shipped worldwide from our Dubai warehouse. Transit, routes and documentation for 136 destinations
From the blog
Written about this part
Heat-transfer tubes
Integral low-fin tube for condenser and cooler retubing
Low-fin tube is rolled out of the tube wall itself, adding outside surface to a shell-and-tube bundle without changing the tube sheet. What it is, where it helps, the standards and materials, and how to order it — with the live size table.
4 min read
Heat-transfer tubes
Copper-nickel 90/10 vs 70/30 vs admiralty brass in seawater cooling
Condenser and cooler tube for seawater, brackish and cooling-tower water: how admiralty brass, aluminium brass and 90/10, 70/30 and 66-30-2-2 copper-nickel differ, the water velocities each tolerates, and how to order them to ASTM B111.