Integral Low-Fin Tubes

Low fins rolled out of the tube wall itself, with plain ends left unfinned. Made to ASTM A498/A498M, ASTM A1012, ASTM B359 / ASME SB359. Supplied from Dubai with an Indus part number for each size and mill test certificates on request.
Key features
- Product type: Integral Low-Fin Tubes
- Standards: ASTM A498/A498M, ASTM A1012, ASTM B359 / ASME SB359, ASTM B891, ASTM B924, ASME VIII-1 UG-8(b), ASTM A179, ASTM A213, BS 3602/1
- Base tube material: CS SA-179, SA-214, SA-334 Gr 1/3/6; Ferritic stainless 405/410/430/439; Austenitic 304/316/317/321; Duplex 2205/2101; 6Mo (N08367); Ni alloys 600/625/800/825/C-276; Alloy 400 (N04400); Ti Gr 1/2/16/26
- Fin material: integral (same as tube)
- Outside diameter: 15.875–25.4 mm
- Wall thickness: 1.829–2.769 mm
- Product type
- Integral Low-Fin Tubes
- Base tube material
- CS SA-179, SA-214, SA-334 Gr 1/3/6; Ferritic stainless 405/410/430/439; Austenitic 304/316/317/321; Duplex 2205/2101; 6Mo (N08367); Ni alloys 600/625/800/825/C-276; Alloy 400 (N04400); Ti Gr 1/2/16/26
- Fin material
- integral (same as tube)
Product description
Low fins rolled out of the tube wall itself, with plain ends left unfinned. The fin tips are no larger than the plain-end OD, so the tubes fit the same tube-sheet and baffle holes as plain tube while carrying several times the outside surface. Used in condensers, chillers and shell-and-tube exchangers where the shell side limits the duty.
Specification
- Plain-end OD (mm): 15.875–25.4 (5/8, 3/4, 7/8, 1 in)
- Fin densities offered: 19, 26, 28, 30, 36 FPI (748–1417 fins/m)
- Fin height 19 FPI (mm): ≈1.35–1.40 (0.053–0.055 in)
- Fin height 26 FPI (mm): 1.245 (0.049 in)
- Fin height 28 FPI (mm): 0.889 (0.035 in)
- Fin thickness avg (mm): 0.28–0.36
- Tolerances: FPI +3/−2; fin height ±0.076 mm; transition 12.7–101.6 mm; land length ≥25.4 mm
- Max length (m): >13.4 (length tolerance bands run past 44 ft)
Standards
ASTM A498/A498M, ASTM A1012, ASTM B359 / ASME SB359, ASTM B891, ASTM B924, ASME VIII-1 UG-8(b), ASTM A179, ASTM A213, BS 3602/1. Equivalent grades across ASTM, EN, DIN, JIS and GB/T standards are indicative; we check them against each tender.
Materials
- Tube: CS SA-179, SA-214, SA-334 Gr 1/3/6; Ferritic stainless 405/410/430/439; Austenitic 304/316/317/321; Duplex 2205/2101; 6Mo (N08367); Ni alloys 600/625/800/825/C-276; Alloy 400 (N04400); Ti Gr 1/2/16/26
- Fins: integral (same as tube)
Testing and documents
- A498: pressure test every tube
- Air test 250 psi (1.72 MPa) after finning, straight tubes; hydro optional
- Eddy current after finning, all tubes
- U-bends hydrotested after bending
- Mill test certificate to EN 10204 3.1 on request; third-party inspection can be arranged against your inspection and test plan
Where it is used
- Cu-Ni low-fin tubes for seawater-cooled condensers
- Shell-and-tube coolers and condensers in gas plants and refineries where shell-side coefficient is limiting
Sizes
11 sizes, each under its own Indus part number in the size table. The table lists typical sizes for the range; other sizes are made on request.
Ordering
Quote the Indus part number from the size table, or send the standard and grade, the outside diameter and wall (BWG or millimetres, minimum or average wall), the length and the quantity, with the fin type, material, height, thickness and fins per inch, and the bare length at each end. We quote with the mill certificates and the inspection you need.
Identification
| Parameter | Value |
|---|---|
| Product type | Integral Low-Fin Tubes |
Compliance
| Parameter | Value |
|---|---|
| Standards | ASTM A498/A498M, ASTM A1012, ASTM B359 / ASME SB359, ASTM B891, ASTM B924, ASME VIII-1 UG-8(b), ASTM A179, ASTM A213, BS 3602/1 |
Construction
| Parameter | Value |
|---|---|
| Base tube material | CS SA-179, SA-214, SA-334 Gr 1/3/6; Ferritic stainless 405/410/430/439; Austenitic 304/316/317/321; Duplex 2205/2101; 6Mo (N08367); Ni alloys 600/625/800/825/C-276; Alloy 400 (N04400); Ti Gr 1/2/16/26 |
| Fin material | integral (same as tube) |
Dimensions
| Parameter | Value |
|---|---|
| Outside diameter | 15.875–25.4 mm |
| Wall thickness | 1.829–2.769 mm |
| Length | >13.4 (length tolerance bands run past 44 ft) |
| Size table | Typical sizes — other sizes on request |
Quality
| Parameter | Value |
|---|---|
| Testing | A498: pressure test every tube; Air test 250 psi (1.72 MPa) after finning, straight tubes; hydro optional; Eddy current after finning, all tubes; U-bends hydrotested after bending |
| Certification | Mill test certificate to EN 10204 3.1 on request; third-party inspection by arrangement |
Application
| Parameter | Value |
|---|---|
| Typical services | Cu-Ni low-fin tubes for seawater-cooled condensers; Shell-and-tube coolers and condensers in gas plants and refineries where shell-side coefficient is limiting |
Shipping & lead time
Sizes & part numbers
11 sizes- Indus part no.IH-TF-IL-ILF-0190-183-H014
- O.D. (mm)
- 19.05
- O.D. (in)
- 3/4
- Wall (mm)
- 1.829
- Fin height (mm)
- 1.397
- Fins per inch
- 19
- Fins per metre
- 748
- Root dia. (mm)
- 16.256
- Wall under fin (mm)
- 1.245
- Material
- 300 stainless; Cu-Ni
- Indus part no.IH-TF-IL-ILF-0190-224-H014
- O.D. (mm)
- 19.05
- O.D. (in)
- 3/4
- Wall (mm)
- 2.235
- Fin height (mm)
- 1.397
- Fins per inch
- 19
- Fins per metre
- 748
- Root dia. (mm)
- 16.256
- Wall under fin (mm)
- 1.651
- Material
- 300 stainless; Cu-Ni
- Indus part no.IH-TF-IL-ILF-0254-224-H014
- O.D. (mm)
- 25.4
- O.D. (in)
- 1
- Wall (mm)
- 2.235
- Fin height (mm)
- 1.397
- Fins per inch
- 19
- Fins per metre
- 748
- Root dia. (mm)
- 22.606
- Wall under fin (mm)
- 1.651
- Material
- 300 stainless; Cu-Ni
- Indus part no.IH-TF-IL-ILF-0254-277-H014
- O.D. (mm)
- 25.4
- O.D. (in)
- 1
- Wall (mm)
- 2.769
- Fin height (mm)
- 1.397
- Fins per inch
- 19
- Fins per metre
- 748
- Root dia. (mm)
- 22.606
- Wall under fin (mm)
- 2.108
- Material
- 300 stainless; Cu-Ni
- Indus part no.IH-TF-IL-ILF-0159-183-H012
- O.D. (mm)
- 15.875
- O.D. (in)
- 5/8
- Wall (mm)
- 1.829
- Fin height (mm)
- 1.245
- Fins per inch
- 26
- Fins per metre
- 1024
- Root dia. (mm)
- 13.386
- Wall under fin (mm)
- 1.245
- Material
- CS; 400 ferritic; Cu-Ni; Alloy 400 (N04400)
- Indus part no.IH-TF-IL-ILF-0190-183-H012
- O.D. (mm)
- 19.05
- O.D. (in)
- 3/4
- Wall (mm)
- 1.829
- Fin height (mm)
- 1.245
- Fins per inch
- 26
- Fins per metre
- 1024
- Root dia. (mm)
- 16.561
- Wall under fin (mm)
- 1.245
- Material
- CS; 400 ferritic; Cu-Ni; Alloy 400 (N04400)
- Indus part no.IH-TF-IL-ILF-0190-211-H012
- O.D. (mm)
- 19.05
- O.D. (in)
- 3/4
- Wall (mm)
- 2.108
- Fin height (mm)
- 1.245
- Fins per inch
- 26
- Fins per metre
- 1024
- Root dia. (mm)
- 16.561
- Wall under fin (mm)
- 1.651
- Material
- CS; 400 ferritic; Cu-Ni; Alloy 400 (N04400)
- Indus part no.IH-TF-IL-ILF-0254-183-H012
- O.D. (mm)
- 25.4
- O.D. (in)
- 1
- Wall (mm)
- 1.829
- Fin height (mm)
- 1.245
- Fins per inch
- 26
- Fins per metre
- 1024
- Root dia. (mm)
- 22.911
- Wall under fin (mm)
- 1.245
- Material
- CS; 400 ferritic; Cu-Ni; Alloy 400 (N04400)
Show all 11 sizesShow fewer sizes
- Indus part no.IH-TF-IL-ILF-0254-211-H012
- O.D. (mm)
- 25.4
- O.D. (in)
- 1
- Wall (mm)
- 2.108
- Fin height (mm)
- 1.245
- Fins per inch
- 26
- Fins per metre
- 1024
- Root dia. (mm)
- 22.911
- Wall under fin (mm)
- 1.651
- Material
- CS; 400 ferritic; Cu-Ni; Alloy 400 (N04400)
- Indus part no.IH-TF-IL-ILF-0190-183-H009
- O.D. (mm)
- 19.05
- O.D. (in)
- 3/4
- Wall (mm)
- 1.829
- Fin height (mm)
- 0.889
- Fins per inch
- 28
- Fins per metre
- 1102
- Root dia. (mm)
- 17.272
- Wall under fin (mm)
- 1.245
- Material
- Ti; Zr; 300 stainless; Ni alloys; 6Mo (N08367)
- Indus part no.IH-TF-IL-ILF-0254-183-H009
- O.D. (mm)
- 25.4
- O.D. (in)
- 1
- Wall (mm)
- 1.829
- Fin height (mm)
- 0.889
- Fins per inch
- 28
- Fins per metre
- 1102
- Root dia. (mm)
- 23.622
- Wall under fin (mm)
- 1.245
- Material
- Ti; Zr; 300 stainless; Ni alloys; 6Mo (N08367)
O.D. (mm) — Outside diameter of the tube or pipe in millimetres. O.D. (in) — The same outside diameter in inches, as the trade orders it. Wall (mm) — Wall thickness in millimetres: minimum or average wall per the governing standard and the order. Fin height (mm) — Height of the fin above the tube surface in millimetres. Fins per inch — Fin density in fins per inch; a band means any density in it can be made. Fins per metre — The same fin density in fins per metre. Root dia. (mm) — Diameter at the root of the fins, in millimetres. Wall under fin (mm) — Average wall thickness under the fins, in millimetres. Material — Tube materials this size is made in, as published.
These are typical sizes for the range, not a full mill list. Other diameters, walls, fin geometries and lengths are made to order: tell us the standard and grade, the O.D. and wall, and the length you need. Mill test certificates to EN 10204 3.1 are available on request.
What are integral low-fin tubes used for?▾
How do I read an integral low-fin part number such as IH-TF-IL-ILF-0254-211-H012?▾
What sizes do integral low-fin tubes come in?▾
What fin density should I choose for integral low-fin tubes?▾
What is the fin tolerance on integral low-fin tubes?▾
What materials are integral low-fin tubes made from?▾
Which standards apply to integral low-fin tubes?▾
What tests are done on integral low-fin tubes?▾
Integral low-fin tube or plain tube for a shell-and-tube condenser?▾
Can integral low-fin tubes be bent into U-tubes?▾
Where are integral low-fin tubes used?▾
Do you supply integral low-fin tubes from Dubai?▾
Shipped worldwide from our Dubai warehouse. Transit, routes and documentation for 136 destinations
From the blog
Written about this part
Heat-transfer tubes
Integral low-fin tube for condenser and cooler retubing
Low-fin tube is rolled out of the tube wall itself, adding outside surface to a shell-and-tube bundle without changing the tube sheet. What it is, where it helps, the standards and materials, and how to order it — with the live size table.
4 min read
Heat-transfer tubes
Finned and seamless heat-transfer tube: a buyer’s guide
How to specify tube for air coolers, shell-and-tube exchangers, condensers, boilers and fired heaters: the standard and grade, OD and wall, length, fin type and bend schedule — and what to send with an enquiry so the quotation matches the data sheet.
6 min read