Copper-Nickel Condenser Tubes — 90/10 and 70/30

90/10 (C70600, CuNi10Fe1Mn) and 70/30 (C71500, CuNi30Mn1Fe) copper-nickel tubes to ASTM B111 and EN 12451, the standard tube for seawater-cooled condensers, coolers and desalination plants. Made to ASTM B111/B111M, ASTM B359, ASTM B395. Supplied from Dubai with an Indus part number for each size and mill test certificates on request.
Key features
- Product type: Copper-Nickel Condenser Tubes
- Construction: Seamless drawn
- Standards: ASTM B111/B111M, ASTM B359, ASTM B395, ASTM B466, EN 12451, ASTM B858, ASTM B154, BS 2871, IS 1545, JIS H 3300
- Base tube material: C70600 / CW352H 90-10; C70620 90-10 welding grade; C71500 / CW354H 70-30; C71520 70-30 welding grade; C71640 / CW353H 66-30-2-2
- Outside diameter: 9.53–25.4 mm
- Wall thickness: 0.89–1.65 mm
- Product type
- Copper-Nickel Condenser Tubes
- Construction
- Seamless drawn
- Base tube material
- C70600 / CW352H 90-10; C70620 90-10 welding grade; C71500 / CW354H 70-30; C71520 70-30 welding grade; C71640 / CW353H 66-30-2-2
Product description
90/10 (C70600, CuNi10Fe1Mn) and 70/30 (C71500, CuNi30Mn1Fe) copper-nickel tubes to ASTM B111 and EN 12451, the standard tube for seawater-cooled condensers, coolers and desalination plants.
Specification
- Maximum design water velocity in tube: 90/10 Cu-Ni 2.4–2.5 m/s in condenser tube (3.5 m/s applies to large-bore pipe only); 70/30 tolerates higher velocity than 90/10
- Max OD in ASTM B111 (mm): 80 (3-1/8 in)
- Tempers: C70600: O61 or H55; C71500 & C71640: O61 or HR50
- Tensile / yield min, C70600 (MPa): O61 275/105; H55 310/240
- Tensile / yield min, C71500 (MPa): O61 360/125; HR50 495/345
- Tensile / yield min, C71640 (MPa): O61 435/170; HR50 560/400
- EN 12451 annealed CuNi10Fe1Mn: R290: Rm 290, Rp0.2 90 MPa, A 30%
- Other common sizes: 5/8×0.035 in, 3/4×0.035 in, 1×0.049 in, 1×0.120 in
- Hydrostatic test basis: fibre stress 48 MPa (7000 psi), P = 2St/(D−0.8t), not above 7.0 MPa unless specified; or pneumatic 400 kPa for 5 s; eddy current is the default NDT
Standards
ASTM B111/B111M, ASTM B359, ASTM B395, ASTM B466, EN 12451, ASTM B858, ASTM B154, BS 2871, IS 1545, JIS H 3300, NES 779. Equivalent grades across ASTM, EN, DIN, JIS and GB/T standards are indicative; we check them against each tender.
Materials
- Tube: C70600 / CW352H 90-10; C70620 90-10 welding grade; C71500 / CW354H 70-30; C71520 70-30 welding grade; C71640 / CW353H 66-30-2-2
Testing and documents
- Eddy current per E243 (each tube) or hydrostatic/pneumatic alternative
- Expansion pin test B153: 30% O61, 20% H55/HR50
- Flattening at three places to 3× wall
- Grain size 0.010–0.045 mm for O61
- Mill test certificate to EN 10204 3.1 on request; third-party inspection can be arranged against your inspection and test plan
Where it is used
- MSF desalination heat-recovery and heat-rejection tubing; C71640 for the heat-rejection section where impingement is severe
- Seawater-cooled condensers and coolers in power, refinery and LNG plants
- Shipboard and offshore seawater coolers
Sizes
7 sizes, each under its own Indus part number in the size table. These are the common sizes; others are made on request.
Ordering
Quote the Indus part number from the size table, or send the standard and grade, the outside diameter and wall (BWG or millimetres, minimum or average wall), the length and the quantity. We quote with the mill certificates and the inspection you need.
Identification
| Parameter | Value |
|---|---|
| Product type | Copper-Nickel Condenser Tubes |
| Construction | Seamless drawn |
Compliance
| Parameter | Value |
|---|---|
| Standards | ASTM B111/B111M, ASTM B359, ASTM B395, ASTM B466, EN 12451, ASTM B858, ASTM B154, BS 2871, IS 1545, JIS H 3300 |
Construction
| Parameter | Value |
|---|---|
| Base tube material | C70600 / CW352H 90-10; C70620 90-10 welding grade; C71500 / CW354H 70-30; C71520 70-30 welding grade; C71640 / CW353H 66-30-2-2 |
Dimensions
| Parameter | Value |
|---|---|
| Outside diameter | 9.53–25.4 mm |
| Wall thickness | 0.89–1.65 mm |
| Length | Random or fixed lengths; cut to length on request |
| Size table | Common sizes |
Performance
| Parameter | Value |
|---|---|
| Water velocity in tube | 90/10 Cu-Ni 2.4–2.5 m/s in condenser tube (3.5 m/s applies to large-bore pipe only); 70/30 tolerates higher velocity than 90/10 |
Quality
| Parameter | Value |
|---|---|
| Testing | Eddy current per E243 (each tube) or hydrostatic/pneumatic alternative; Expansion pin test B153: 30% O61, 20% H55/HR50; Flattening at three places to 3× wall; Grain size 0.010–0.045 mm for O61 |
| Certification | Mill test certificate to EN 10204 3.1 on request; third-party inspection by arrangement |
Application
| Parameter | Value |
|---|---|
| Typical services | MSF desalination heat-recovery and heat-rejection tubing; C71640 for the heat-rejection section where impingement is severe; Seawater-cooled condensers and coolers in power, refinery and LNG plants; Shipboard and offshore seawater coolers |
Shipping & lead time
Sizes & part numbers
7 sizes- Indus part no.IH-TF-CN-CUN-0095-089
- O.D. (mm)
- 9.53
- O.D. (in)
- 3/8
- BWG
- 20
- Wall (mm)
- 0.89
- Wall (in)
- 0.035
- Indus part no.IH-TF-CN-CUN-0095-124
- O.D. (mm)
- 9.53
- O.D. (in)
- 3/8
- BWG
- 18
- Wall (mm)
- 1.24
- Wall (in)
- 0.049
- Indus part no.IH-TF-CN-CUN-0127-124
- O.D. (mm)
- 12.70
- O.D. (in)
- 1/2
- BWG
- 18
- Wall (mm)
- 1.24
- Wall (in)
- 0.049
- Indus part no.IH-TF-CN-CUN-0159-124
- O.D. (mm)
- 15.88
- O.D. (in)
- 5/8
- BWG
- 18
- Wall (mm)
- 1.24
- Wall (in)
- 0.049
- Indus part no.IH-TF-CN-CUN-0190-124
- O.D. (mm)
- 19.05
- O.D. (in)
- 3/4
- BWG
- 18
- Wall (mm)
- 1.24
- Wall (in)
- 0.049
- Indus part no.IH-TF-CN-CUN-0190-165
- O.D. (mm)
- 19.05
- O.D. (in)
- 3/4
- BWG
- 16
- Wall (mm)
- 1.65
- Wall (in)
- 0.065
- Indus part no.IH-TF-CN-CUN-0254-165
- O.D. (mm)
- 25.40
- O.D. (in)
- 1
- BWG
- 16
- Wall (mm)
- 1.65
- Wall (in)
- 0.065
O.D. (mm) — Outside diameter of the tube or pipe in millimetres. O.D. (in) — The same outside diameter in inches, as the trade orders it. BWG — Birmingham Wire Gauge of the wall, the usual way heat-exchanger tube wall is ordered. Wall (mm) — Wall thickness in millimetres: minimum or average wall per the governing standard and the order. Wall (in) — The same wall thickness in inches.
These are typical sizes for the range, not a full mill list. Other diameters, walls, fin geometries and lengths are made to order: tell us the standard and grade, the O.D. and wall, and the length you need. Mill test certificates to EN 10204 3.1 are available on request.
What are Copper-Nickel Condenser Tubes, 90/10 and 70/30 used for?▾
How do I read an Indus part number for Copper-Nickel Condenser Tubes, 90/10 and 70/30, such as IH-TF-CN-CUN-0095-089?▾
What sizes do Copper-Nickel Condenser Tubes, 90/10 and 70/30 come in?▾
What do I need to send to order Copper-Nickel Condenser Tubes, 90/10 and 70/30 to the right size and grade?▾
What cooling-water velocity can Copper-Nickel Condenser Tubes, 90/10 and 70/30 take?▾
What tests and certificates come with Copper-Nickel Condenser Tubes, 90/10 and 70/30?▾
Which materials and grades are Copper-Nickel Condenser Tubes, 90/10 and 70/30 available in?▾
Which standards apply to Copper-Nickel Condenser Tubes, 90/10 and 70/30?▾
What do Copper-Nickel Condenser Tubes, 90/10 and 70/30 connect to or fit with?▾
How should Copper-Nickel Condenser Tubes, 90/10 and 70/30 be inspected on receipt and stored?▾
How are Copper-Nickel Condenser Tubes, 90/10 and 70/30 shipped, and can they be exported from Dubai?▾
Do you keep Copper-Nickel Condenser Tubes, 90/10 and 70/30 in stock in Dubai?▾
Shipped worldwide from our Dubai warehouse. Transit, routes and documentation for 136 destinations
From the blog
Written about this part
Heat-transfer tubes
Copper-nickel 90/10 vs 70/30 vs admiralty brass in seawater cooling
Condenser and cooler tube for seawater, brackish and cooling-tower water: how admiralty brass, aluminium brass and 90/10, 70/30 and 66-30-2-2 copper-nickel differ, the water velocities each tolerates, and how to order them to ASTM B111.
3 min read
Heat-transfer tubes
Reading a mill test certificate to EN 10204 3.1
Every length of pressure tube should be traceable to a certificate. What EN 10204 types 2.1, 2.2, 3.1 and 3.2 mean, what a 3.1 certificate for tube should contain, and the checks to make before the tube goes into a bundle.
3 min read